Data link layer options, Device address binding, Networking options – GE Industrial Solutions A Series Lighting Control Panelboards BACnet Protocol User Manual
Page 6: Character sets supported, A series

A Series
®
Lighting Controller
BACnet Protocol Implementation Conformance Statement
6
Data Link Layer Options
Options
Notes
; BACnet IP, (Annex J)
Only supported by Ethernet-capable products.
; BACnet IP, (Annex J), Foreign Device
Only supported by Ethernet-capable products.
; ISO 8802-3, Ethernet (Clause 7) (10Base2, 10Base5, 10BaseT, Fiber)
Only supported by Ethernet-capable products.
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s):
; MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
MS/TP slave (Clause 9), baud rate(s):
; Point-To-Point, EIA 232 (Clause 10), baud rate(s): 9600, 1920, 38400
; Point-To-Point, modem, (Clause 10), baud rate(s): 9600, 19200, 38400
LonTalk, (Clause 11), medium:
Other:
Device Address Binding
Is static device binding supported?
; Yes
No
(Necessary for two-way communication with MS/TP slaves and certain other devices.)
Networking Options
Router
;
Router between Ethernet, BACnet/IP, MS/TP and PTP or
between MS/TP and PTP (model dependent).
Annex H, BACnet Tunneling
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign
Devices?
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
; ANSI X3.4
IBM/Microsoft DBCS
JIS C 6226
ISO 10646 (ICS-4)
ISO 10646 (UCS2)
ISO 8859-1
If this product is a communication gateway, describe the types of
non-BACnet equipment/networks(s) that the gateway supports
Not applicable.