Entelliguard tu trip unit test procedure, Initial trip unit set-up, Set ground fault pick-up to 0.20 – GE Industrial Solutions EntelliGuard G Digital Test Kit User Manual

Page 6: Scroll to event tab on main screen, Metering test, Breaker trip test, Ground fault test, Overload (long time) test

Entelliguard tu trip unit test procedure, Initial trip unit set-up, Set ground fault pick-up to 0.20 | Scroll to event tab on main screen, Metering test, Breaker trip test, Ground fault test, Overload (long time) test | GE Industrial Solutions EntelliGuard G Digital Test Kit User Manual | Page 6 / 8 Entelliguard tu trip unit test procedure, Initial trip unit set-up, Set ground fault pick-up to 0.20 | Scroll to event tab on main screen, Metering test, Breaker trip test, Ground fault test, Overload (long time) test | GE Industrial Solutions EntelliGuard G Digital Test Kit User Manual | Page 6 / 8