Ge energy, Car2548tn series rectifier, Absolute maximum ratings – GE Industrial Solutions CAR2548TN series User Manual
Page 2: Electrical specifications
GE Energy
CAR2548TN series rectifier
Input: 90Vac to 264Vac; Output: -54 Vdc @ 2500W; 3.3Vdc or 5 Vdc @ 1A
April 23, 2013
©2012 General Electric Company. All rights reserved.
Page 2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter
Device
Symbol
Min
Max
Unit
Input Voltage: Continuous
All
VIN
0
264
Vac
Operating Ambient Temperature
All
TA
-10
70
1
°C
Storage Temperature
All
Tstg
-40
85
°C
I/O Isolation voltage (100% factory Hi-Pot tested)
All
1500
Vdc
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Device
Symbol
Min
Typ
Max
Unit
Operational Range
All
V
IN
90
110/230
264
V
ac
Frequency Range (ETSI 300-132-1 recommendation)
All
F
IN
47 50/60 63 Hz
High Line Operation 180 – 264 Vac
All
W
0 -
2500
W
Low Line Operation 90 – 132 Vac
All
W
0 -
1200
W
Main Output Turn_OFF
All
V
IN
85
V
ac
Maximum Input Current V
IN
= 90Vac
All I
IN
16
16
A
ac
(V
O
= V
O, set
, I
O
=I
O, max
) V
IN
= 180Vac
Cold Start Inrush Current
All I
IN
50
A
peak
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
Efficiency
All
92
%
(T
amb
=25C, V
in
= 230Vac, V
out
= 54Vdc)
Power Factor
(V
in
=230Vac, I
O
=I
O, max
)
All
PF 0.99
Holdup time
(V
in
= 230Vac, V
out
= -54V
dc
, T
amb
25C,
I
O
=I
O, max
)
All
T 16.8
ms
Loss of Output Early Warning Signal
2
ms
Ride through
All
T 8.3
ms
Leakage Current
(V
in
= 250Vac, F
in
= 60Hz)
All
I
IN
3
mArms
Isolation Input/Output
All
3000 V
ac
Input/Frame
1500
V
ac
Output/Frame
100
V
dc
-54V
dc
MAIN OUTPUT
Parameter
Device
Symbol
Min
Typ
Max
Unit
Output power
All
P
out
0
2500
W
dc
Set point
All
V
out
-53.94 -54.00 -54.06 V
dc
Overall regulation (load, temperature, aging)
All
-2 +2
%
Ripple and noise
2
All
540
mV
p-p
Turn-ON overshoot
All
+3
%
Turn-ON delay
All
T 2
sec
1
Derated above 50C at 2.5%/C
2
Measured across a 10µf electrolytic and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth