GE Industrial Solutions Spectra Series Power Panelboards 60 A_600 V, 100 A_240 V, 100 A_600 User Manual
Spectra series™ power panelboards, Installing the expansion kit

g
Spectra Series™ Power Panelboards
60 A/600 V, 100 A/240 V, 100 A/600 V Expansion Kits for
Type ADS Fusible Switch Units
WARNING: Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
.
Do
not remove circuit protective devices or any
other component until the power is turned
OFF.
Installing the Expansion Kit
1. Remove the fusible switch unit from the panelboard
or switchboard. Remove the load-side wires from the
switch load-side terminal. Loosen the rail latch
screws on each side of the switch unit and remove
the switch by pulling up on both latch handles, as
shown in Figure 1, while pulling the device from the
panelboard.
2. Prepare the enclosure. Remove and discard the
blank cover and the bottom insulator from the
bottom of the device, as shown in Figure 2.
3. Install the straps. Install the connecting straps with
the #10-32 x
1
/
2
" mounting screws provided, as
shown in Figure 3. Tighten the screws to 27–32 in-lb.
Figure 1. Removing the fusible switch from the equipment.
Figure 2. Removing the blank cover and bottom insulator.
Figure 3. Installing the connecting straps.
GEH5581 Installation Instructions
R03
Rail Latch
Screw
Latch
Handle
Bottom Fiber
Insulator
Blank
Cover
Connecting
Strap
#10-32 x
1
/
2
"
Screw