beautypg.com

Part numbers & speci fications, Single phase, 3 phase delta / 3 phase wye, common n/g – GE Industrial Solutions Tranquell DIN Rail Mount Series SPD (UL recognized) User Manual

Page 2: 3 phase high leg delta / 3 phase wye, plus n-g, Split phase, Figure 4 – wiring con figuration diagram, Wire installation #14, 08 mm, 3 mm, Rohs

background image

GE

Digital Energy – Power Quality

830

W 40th Street, Chicago, IL 60609 USA

800 637 1738

www.gepowerquality.com

Information subject to change without notice. Please verify all details with GE.

© 2010 General Electric Company All Rights Reserved

Figure 4 – Wiring Con

figuration Diagram

(NOTE: Shown with no power applied)

NOTE: The Tranquell

DIN

Rail SPD has been tested for safe operation without any

additional overcurrent protection, when correctly matched to the power system
parameters. A gG 160 Amp NH Fuse may be chosen to meet other requirements in
an IEC application. Consult local codes and standards for appropriate fuse sizing.

G/N

L

SINGLE

PHASE

L1

L2

L3

G/N

3 PHASE DELTA /

3 PHASE WYE, COMMON N/G

L1

L2

L3

N

G

3 PHASE HIGH LEG DELTA /

3 PHASE WYE, PLUS N-G

L1

L2

G/N

SPLIT

PHASE

Part Numbers & Speci

fications

4. WIRE INSTALLATION

#14

AWG

to #6

AWG

(2.08 mm

2

- 13.3 mm

2

), 60/75°C Copper

wire shall be used on phase and Neutral/

PE

terminals.

Maximum torque to be applied to terminal screws is
14.75 in.-lb. (2.0 N-m). Strip back wire insulation 1/4" (6 mm).

Interconnecting wire should be kept at minimum length. Wire
bending radius should be > 4" (100 mm). Do not loop or twist
interconnecting wire. Failure to meet these requirements may
result in higher let-through voltages.

Tranquell

SPD is normally installed in parallel with the load or

the electrical system wiring.

Determine electrical voltage configuration and proper modes
of protection and install wiring as shown in Figure 4.

Assembly System

Part Number

Wiring

Con

figuration

L-N/G Pluggable Module

N - G Pluggable Module

Hi-Leg Pluggable Module

No. of

Poles

No. of
Wires

Part Number

Qty

Part Number

Qty

Part Number

Qty

TD120Y4025RMN

3 Phase Wye,

plug N-G

RU-180-25

3

RU-180-25

1

4

5

TD120Y4050RMN

RU-180-50

RU-180-50

TD277Y4025RMN

RU-320-25

RU-180-25

TD277Y4050RMN

RU-320-50

RU-180-50

TD347Y4025RMN

RU-420-25

RU-275-25

TD347Y4050RMN

RU-420-50

RU-275-50

TD240H4025RMN

3 Phase

High Leg Delta

RU-180-25

2

RU-180-25

RU-275-25

1

TD240H4050RMN

RU-180-50

RU-180-50

RU-275-50

TD480H4025RMN

RU-275-25

RU-180-25

RU-550-25

TD480H4050RMN

RU-275-50

RU-180-50

RU-550-50

TD120Y3025RMP

3 Phase Wye

common N/G

RU-180-25

3

3

4

TD120Y3050RMP

RU-180-50

TD277Y3025RMP

RU-320-25

TD277Y3050RMP

RU-320-50

TD347Y3025RMP

RU-420-25

TD347Y3050RMP

RU-420-50

TD240D3025RMP

3 Phase Delta

RU-275-25

TD240D3050RMP

RU-275-50

TD480D3025RMP

RU-550-25

TD480D3050RMP

RU-550-50

TD120S2025RMP

Split Phase

RU-180-25

2

2

3

TD120S2050RMP

RU-180-50

TD240S2025RMP

RU-275-25

TD240S2050RMP

RU-275-50

TD120S1025RMP

Single Phase

RU-180-25

1

1

2

TD120S1050RMP

RU-180-50

TD240S1025RMP

RU-275-25

TD240S1050RMP

RU-275-50

TD277S1025RMP

RU-320-25

TD277S1050RMP

RU-320-50

TD347S1025RMP

RU-420-25

TD347S1050RMP

RU-420-50

2020007801 (3/10)

COMPLIANT
2002/95/EC

RoHS