Part numbers & speci fications, Single phase, 3 phase delta / 3 phase wye, common n/g – GE Industrial Solutions Tranquell DIN Rail Mount Series SPD (UL recognized) User Manual
Page 2: 3 phase high leg delta / 3 phase wye, plus n-g, Split phase, Figure 4 – wiring con figuration diagram, Wire installation #14, 08 mm, 3 mm, Rohs
GE
Digital Energy – Power Quality
830
W 40th Street, Chicago, IL 60609 USA
800 637 1738
www.gepowerquality.com
Information subject to change without notice. Please verify all details with GE.
© 2010 General Electric Company All Rights Reserved
Figure 4 – Wiring Con
figuration Diagram
(NOTE: Shown with no power applied)
NOTE: The Tranquell
™
DIN
Rail SPD has been tested for safe operation without any
additional overcurrent protection, when correctly matched to the power system
parameters. A gG 160 Amp NH Fuse may be chosen to meet other requirements in
an IEC application. Consult local codes and standards for appropriate fuse sizing.
G/N
L
SINGLE
PHASE
L1
L2
L3
G/N
3 PHASE DELTA /
3 PHASE WYE, COMMON N/G
L1
L2
L3
N
G
3 PHASE HIGH LEG DELTA /
3 PHASE WYE, PLUS N-G
L1
L2
G/N
SPLIT
PHASE
Part Numbers & Speci
fications
4. WIRE INSTALLATION
#14
AWG
to #6
AWG
(2.08 mm
2
- 13.3 mm
2
), 60/75°C Copper
wire shall be used on phase and Neutral/
PE
terminals.
Maximum torque to be applied to terminal screws is
14.75 in.-lb. (2.0 N-m). Strip back wire insulation 1/4" (6 mm).
Interconnecting wire should be kept at minimum length. Wire
bending radius should be > 4" (100 mm). Do not loop or twist
interconnecting wire. Failure to meet these requirements may
result in higher let-through voltages.
Tranquell
™
SPD is normally installed in parallel with the load or
the electrical system wiring.
Determine electrical voltage configuration and proper modes
of protection and install wiring as shown in Figure 4.
Assembly System
Part Number
Wiring
Con
figuration
L-N/G Pluggable Module
N - G Pluggable Module
Hi-Leg Pluggable Module
No. of
Poles
No. of
Wires
Part Number
Qty
Part Number
Qty
Part Number
Qty
TD120Y4025RMN
3 Phase Wye,
plug N-G
RU-180-25
3
RU-180-25
1
—
—
4
5
TD120Y4050RMN
RU-180-50
RU-180-50
TD277Y4025RMN
RU-320-25
RU-180-25
TD277Y4050RMN
RU-320-50
RU-180-50
TD347Y4025RMN
RU-420-25
RU-275-25
TD347Y4050RMN
RU-420-50
RU-275-50
TD240H4025RMN
3 Phase
High Leg Delta
RU-180-25
2
RU-180-25
RU-275-25
1
TD240H4050RMN
RU-180-50
RU-180-50
RU-275-50
TD480H4025RMN
RU-275-25
RU-180-25
RU-550-25
TD480H4050RMN
RU-275-50
RU-180-50
RU-550-50
TD120Y3025RMP
3 Phase Wye
common N/G
RU-180-25
3
—
—
—
—
3
4
TD120Y3050RMP
RU-180-50
TD277Y3025RMP
RU-320-25
TD277Y3050RMP
RU-320-50
TD347Y3025RMP
RU-420-25
TD347Y3050RMP
RU-420-50
TD240D3025RMP
3 Phase Delta
RU-275-25
TD240D3050RMP
RU-275-50
TD480D3025RMP
RU-550-25
TD480D3050RMP
RU-550-50
TD120S2025RMP
Split Phase
RU-180-25
2
—
—
—
—
2
3
TD120S2050RMP
RU-180-50
TD240S2025RMP
RU-275-25
TD240S2050RMP
RU-275-50
TD120S1025RMP
Single Phase
RU-180-25
1
—
—
—
—
1
2
TD120S1050RMP
RU-180-50
TD240S1025RMP
RU-275-25
TD240S1050RMP
RU-275-50
TD277S1025RMP
RU-320-25
TD277S1050RMP
RU-320-50
TD347S1025RMP
RU-420-25
TD347S1050RMP
RU-420-50
2020007801 (3/10)
COMPLIANT
2002/95/EC
RoHS