GE Industrial Solutions Tranquell DIN Rail Mount Series SPD (UL recognized) User Manual
Installation, operation & maintenance manual, Ge digital energy power quality, Tranquell
GE Digital Energy
Power Quality
Installation, Operation &
Maintenance Manual
Tranquell
™
Surge Protective Device (
SPD
)
UL
Recognized
DIN R
ail Mount
•
This equipment must be
installed and serviced only by qualified
electrical personnel in accordance with
national and local electrical codes.
•
Turn off all power supplying this equipment
before working on equipment.
•
Always use a properly rated voltage-sensing
device to confirm power is off.
•
Replace all devices, doors and covers before
restoring power to this equipment.
•
Do not apply petroleum-based products to
nonmetallic parts.
Improper installation or misapplication of these devices
may result in serious injury to the installer and/or
damage to electrical system or related equipment.
Protective eye wear and clothing should be worn
whenever working around hazardous voltages.
Failure to follow these instructions could result in
serious injury or death.
•
Do not attempt to open or
tamper the Tranquell
™
device
in any way as this may com-
promise performance and
will void the warranty.
•
Megger and hi-potential tests may damage
the device. Disconnect all power supplying the
equipment and isolate the Tranquell
™
device
before testing.
•
Install for point-of-use Tranquell
™
DIN
Rail,
tested for Type 2 applications
•
Prior to installation, confirm that the Tranquell
™
SPD
is rated for the correct voltage, current
and frequency equivalent to the application.
•
Tranquell
™
DIN
Rail must be installed within
an enclosure or control cabinet.
•
Operating and storage temperature of this device
must be within -13°F to 140°F (-25°C and +60°C).
D A N G E R
C A U T I O N
Hazard of Electric Shock,
Burn or Explosion
1.
MOUNTING
Tranquell
™
SPD DIN
Rail is designed to
mount onto a 35mm DIN rail or top-hat rail
(standard EN 50022, BS 5584) set in the
horizontal position. To install, first hook the
line side over a 35mm DIN rail and then push in
the load side until the spring loaded mounting
clip “clicks” onto the rail (See Figure 1).
3.
AUXILIARY MICROSWITCH INSTALLATION
Remote signaling is available on Tranquell
™
SPD DIN R
ail products. #30 AWG to #16 AWG
(.051 mm
2
- 1.31 mm
2
) signal wire may be used. Maximum torque rating for the terminal
screw is 1.8 in.-lb. (0.113 N-m). The maximum continuous current rating for the micro-
switch contact is 3 amps. If applicable, install signal wiring as shown in Figure 3.
Figure 3 – Microswitch
Signal Wire Range: #30 AWG to #16 AWG (.051 mm
2
- 1.31 mm
2
)
Terminal Torque: 1.8 in.-lb. (0.113 N-m)
NC
Common
NO
Contact
Rating
125 VAC –
3 amp max.
-25°C to 85°C
Contact between Common + NO
= Product Offline, Not-Protected
Contact between Common + NC
= Product Online, Protected
NOTE
:
Shown with no power applied
Field wiring by others
2.
REPLACEMENT
/
REMOVAL
Replace the module if the
RED
indicator tab (See Figure 2) is visible
on any of the multiple pole units. To remove: (1) verify that you have the correct replacement
module; (2) disconnect power; (3) pull the pluggable module from the base; (4) push a new
pluggable module into the base. You will hear a “click”, indicating that the module is set
in place (See Figure 1). An insertion “key” built into the unit will help ensure that the module
has been correctly selected.
CAUTION
: Use of excessive force, during insertion, can result
in damage to the module or the base.
Figure 2 – Visual Indicator Tab
Figure 1 –
Mounting