Step 6 – Check Breaker
Functions
Perform operational checks to insure proper
functioning of the new accessory.
• For a shunt trip, apply the rated voltage and verify
that the breaker trips.
• For an undervoltage release, apply the rated
voltage to allow the breaker to close, then remove
the voltage and verify that the breaker trips.
See NEMA publication AB4 for further details.