Data sheet, Input; default outputs: ±54v, Digital interface specifications – GE Industrial Solutions CP2000AC54TE User Manual
Page 5
GE
Data Sheet
CP2000AC54TE CPL High Efficiency Rectifier
100-120/200-277V
AC
input; Default Outputs: ±54V
DC
@ 2000W, 5V
DC
@ 4W
August 16, 2013
©2013 General Electric Company. All rights reserved.
Page 5
Feature Specifications (continued)
Parameter
Symbol
Min
Typ
Max
Unit
Power Capacity Logic HI
V
0.7V
DD
12 V
DC
Logic LO
V
0
0.4 V
DC
Reset Logic HI
V
0.7V
DD
12
V
DC
Logic LO
V
0
0.4 V
DC
Protocol select Logic HI - Analog/PMBus™ mode
V
IH
2.7
3.5
V
DC
Logic – intermediate – RS485 mode
V
II
1.0 2.65
V
DC
Logic LO – DSP reprogram mode
V
IL
0
0.4 V
DC
Digital Interface Specifications
Parameter
Conditions
Symbol
Min
Typ
Max
Unit
PMBus Signal Interface Characteristics
Input Logic High Voltage (CLK, DATA)
V
1.5
3.6
V
DC
Input Logic Low Voltage (CLK, DATA)
V
0
0.8
V
DC
Input high sourced current (CLK, DATA)
I
0
10
μA
Output Low sink Voltage (CLK, DATA, SMBALERT#)
I
OUT
=3.5mA V 0.4 V
DC
Output Low sink current (CLK, DATA, SMBALERT#)
I
3.5
mA
Output High open drain leakage current (CLK,DATA,
SMBALERT#)
V
OUT
=3.6V I
0 10 μA
PMBus Operating frequency range
Slave Mode
FPMB
10
400
kHz
Measurement System Characteristics
Clock stretching
T
stretch
25 ms
I
OUT
measurement range
Direct
I
rng
0 50
8
A
DC
I
OUT
measurement accuracy 25°C
I
out(acc)
-2.5
+2.5
% of FL
V
OUT
measurement range
Direct
V
out(rng)
0
70 V
DC
V
OUT
measurement accuracy
9
V
out(acc)
-1 +1 %
Temp measurement range
Direct
Temp
(rng)
0
150
C
Temp measurement accuracy
10
Temp
(acc)
-5 +5 %
V
IN
measurement range
Direct
V
in(rng)
0 320 V
AC
V
IN
measurement accuracy
V
in(acc)
-1.5 +1.5 %
P
IN
measurement range
Direct
P
in(rng)
0 3000 W
in
P
IN
measurement accuracy
11
P
in(acc)
-3.5 +3.5 %
Fan Speed measurement range
Direct
0
30k
RPM
Fan Speed measurement accuracy
-10
10
%
Fan speed control range
Direct
0
100
%
Device Addressing
Unit address [reference: V
OUT
( - )]
Module 1
V
unitadr
2.3 2.477 3.3 V
DC
Module 2
V
unitadr
1.6 1.925 2.2 V
DC
Module 3
V
unitadr
0.9 1.243 1.5 V
DC
Module 4
V
unitadr
0 0.654 0.8 V
DC
Shelf address [reference: V
OUT
( - )]
Shelf 1
V
shelfadr
3.0 3.3 3.45 V
DC
Shelf 2
V
shelfadr
2.7 2.86 2.97 V
DC
Shelf 3
V
shelfadr
2.18 2.4 2.56 V
DC
Shelf 4
V
shelfadr
1.73 1.96 2.14 V
DC
Shelf 5
V
shelfadr
1.29 1.50 1.70 V
DC
Shelf 6
V
shelfadr
0.84 1.10 1.25 V
DC
Shelf 7
V
shelfadr
0.30 0.60 0.80 V
DC
Shelf 8
V
shelfadr
0 0.01 0.25 V
DC
8
Load levels higher than 50A will be read as 50A.
9
Above 2.5A of load current
10
Temperature accuracy reduces non-linearly with decreasing temperature
11
Below 100W input power measurement accuracy reduces significantly