Data sheet, Input; default outputs: ±54v, Table 1: fru_id – GE Industrial Solutions CP2000AC54TE User Manual
Page 17: Table 2: alarm and led state summary

GE
Data Sheet
CP2000AC54TE CPL High Efficiency Rectifier
100-120/200-277V
AC
input; Default Outputs: ±54V
DC
@ 2000W, 5V
DC
@ 4W
August 16, 2013
©2013 General Electric Company. All rights reserved.
Page 17
Table 1: FRU_ID
The upper quarter of memory starting from address 6144 shall be reserved for factory ID and factory data.
Memory
Location
Decimal
Memory
Location
(HEX)
Length
(bytes)
Format
Static
Value
Type
Description
Notes/Example
6144d
0x1800
12
ASCII
Fixed
GE-energy - Product ID
CP2000AC54TE
6156d
0x180C
10
ASCII
Fixed
GE-energy – Part Number
123456789x or C123456789
6166d 0x1816 6 ASCII Variable
GE-energy - Hardware revision
x:xxxx controlled by PDI series #
6172d 0x181C 6 ASCII Variable
spare
6178d 0x1822 14 ASCII Variable
GE-energy - Serial_No
01KZ51018193xx
01 …. Year of manufacture - 2001
KZ … factory, in this case Matamoros
51 .. week of manufacture
______018193xx serial # mfg choice
6192d 0x1830 40 ASCII Variable
GE- Manufacturing location
“Matamoros, Tamps, Mexico”
6232d 0x1858 8 ASCII Fixed
spare
6240d 0x1860 2 HEX Fixed
spare
6242d 0x1862 158 ASCII Fixed
Customer Information
These fields are reserved for use by the
customer.
6400d
0x1900
5
HEX
Fixed
M, B, & R for voltage read
M & B are 2 bytes each sent as MSB and then
LSB. R is one byte. These are stored as two’s
complement.
See the section on Direct Mode Constants
Stored in the EEPROM for the constants stored
in these fields
6405d
0x1905
5
HEX
Fixed
M, B, & R for current read
6410d
0x190A
5
HEX
Fixed
M, B, & R temp read
6415d 0x190F 5 HEX Fixed spare
6420d
0x1914
5
HEX
Fixed
M, B, & R for voltage set
6425d
0x1919
5
HEX
Fixed
M, B, & R for input voltage read
6430d 0x191E 1 HEX Variable
Validation
CHKSUM
6431d
9x191F
5
HEX
Fixed
M, B, & R for input power read
6436d
0x1924
5
HEX
Fixed
M, B, & R for fan percent adjust
6441d
0x1929
5
HEX
Fixed
M, B, & R for fan RPM read
6446d
0 x 192E
5
HEX
Fixed
M, B, & R for converter input
voltage read
Notes:
CHkSUM is a CRC-8 calculation from location 0x1800 to location 0x19FF without including serial number and checksum locations. chksum_value =
0xFF - (mask of SUM with 0x0000ff) write chksum_value byte to location 0x191E.
Table 2: Alarm and LED state summary
Power Supply LED State
Monitoring Signals
Condition
AC OK
Green
DC OK
Green
Service
Amber
Fault
Red
Fault OTW PFW
Module
Present
OK 1
1
0
0
HI HI HI LO
Thermal Alarm (5C before shutdown)
1
1
1
0
HI LO HI LO
Thermal Shutdown
1
0
1
1
LO LO LO LO
Defective Fan
1
0
0
1
LO HI LO LO
Blown AC Fuse in Unit
1
0
0
1
LO HI LO LO
AC Present but not within limits
Blinks
0
0
0
HI HI LO LO
AC not present
1
0 0 0 0
HI HI LO LO
Boost Stage Failure
1
0
0
1
LO HI LO LO
Over Voltage Latched Shutdown
1
0
0
1
LO HI LO LO
Over Current
1
Blinks
0
0
HI HI LO LO
Non-catastrophic Internal Failure
2
1
1
0
1
LO HI HI
LO
Missing Module
HI
Standby (remote)
1
0
0
0
HI HI LO LO
Service Request (PMBus mode)
1
1
Blinks
0
HI HI HI LO
Communications Fault (RS485 mode)
1
1
0
Blinks
HI HI HI LO
1
This signal is correct if the rectifier is back biased from other rectifiers in the shelf .
2
Any detectable fault condition that does not cause a shutting down. For example, ORing FET failure, boost section out of regulation, etc.
3
Signal transition from HI to LO is output load dependent