FsmobSuper700_EN Jul-10

PLC

Parameter

Inlet

Outlet

Instrumentation

GE Fanuc PLC

Flow

X

X

Analog (4-20 mA) to
customer tie-in and/or

discrete tank level for

automatic shut down
and control

Pressure

X

X

pH

X

Temperature

X

Conductivity

X

X

Description

Electrical

1-phase Service:

120 VAC, 60 Hz

Breaker Size:

20 amp

3-phase Service:

480 VAC, 60 Hz

RO Train 1 Breaker size:

400 amp

RO Train 2 Breaker size:

250 amp

Description

Connections

Connection Type:

150# Flange

Train 1 Inlet:

6 inch

Train 1 CIP Inlet:

4 inch

Train 2 Inlet:

6 inch

Train 2 CIP Inlet:

4 inch

Permeate Outlet:

6 inch

Concentrate Outlet

4 inch

Train 1 Permeate CIP Outlet:

4 inch

Train 2 Permeate CIP Outlet:

4 inch

Train 1 Concentrate CIP Outlet

3 inch

Train 2 Concentrate CIP Outlet

3 inch