PowerWalker ViewPower PowerWalker User Manual
Page 39
38
devices when UPS is off. Vice versa.
Converter mode: If enabled, the UPS will operate in converter mode. Vice versa.
ECO mode: If enabled, the UPS will operate in ECO mode when input voltage is
within acceptable range. Vice versa.
Battery open status check: If enabled, the monitored UPS will check if the
battery connection ok or not when UPS is turned on.
Cold start: If disabled, the UPS can be turned on only when AC is normally
connected to UPS. Vice versa.
Bypass not allowed: If enabled, the UPS will not transfer to bypass mode under
any conditions. If disabled, the UPS will be allowed to transfer to bypass mode
according to UPS internal setting.
Battery deep-discharge protection: If enabled, the monitored UPS shutdown in
accordance with the condition of battery and load on battery mode to protect
battery. Vice versa.
Site fault detection: If enabled, the monitored UPS will beep when the input
neutral and hot wires are reversed. Vice versa.
P1 Programmable outlet control (battery mode): If enabled, when UPS is
running at battery mode, it will cut off P1 outlets after backup setting time arrive.
If disabled, UPS will provide continuous power to P1 outlets until the battery is
running out.
Outlet setting: Users can set limited backup time for P1 outlets when UPS is on
battery mode.
Battery numbers setting:
Numbers in parallel: set battery numbers in parallel.
Voltage and frequency range for bypass mode: Set acceptable voltage and
frequency range in bypass mode.
Maximum and minimum voltage: When UPS is on bypass mode and input
voltage is out of setting range, UPS will enter battery mode.
Maximum and minimum frequency: When UPS is on bypass mode and
input frequency is out of setting range, UPS will enter battery mode.