beautypg.com

Troubleshooting, Incorrect reading, Sensor failure – B&B Electronics ISOCON-6 - Manual User Manual

Page 15: Troubleshooting 7.1 incorrect, Reading, 2 sensor, Failure

background image

ISOCON-6 USERS GUIDE

7. TROUBLESHOOTING

The ISOCON has some built in self diagnostic functions. If the LED on the front
panel is flashing then the fault mode can be found by counting the number of flashes
between gaps and using the table below to locate the problem.

No of

Flashes

Nature of Fault

Corrective Action

0

(Green On)

Unit Working – no suspected
fault

Check Wiring and switch
settings

2,3,4,5,6,8,9,

10,11,12

Green

Hardware Error, extreme
noise, poor supply

Switch off unit, check switch
settings, and wiring, and retry.
If still faulty please contact
supplier

7

Green RTD / Thermocouple

burnout

Repair RTD, T/C or wiring

3 or 4 Red Span point is too close to

zero point

Change input span value and
retry

3 or 4

Yellow

Zero point is too close to
span point

Change input zero value and
retry

No LED

Power Failure

Check supply lines and voltage

7.1 Incorrect Reading

Check that Unit is configured for the correct Sensor

Check that Input Scaling is as required.

Check that Linearisation has not been set incorrectly.

Check that Thermocouples have correct compensation cables, and polarity.

Check that RTD is set for correct option 2, 3 or 4 Wire.

Check that RTD leads are connected to appropriate terminal pins.

7.2 Sensor Failure

Check that sensor wiring is correct.

Check Thermocouple polarity.

Check that all RTD leads are connected to correct terminals.

Check that the ISOCON is configured for correct sensor.

Check that applied voltage is not out of range.

Check that applied current is not out of range.

Check that applied millivoltage is out of range.


IIG-010801 Page

15