ISOCON-6 USERS GUIDE
4.1.5 Thermocouple Input
Select the range from the table below and set Switch S1 to the required values.
Switch
K J R S N E
B
T
1
2
3
4
5
6
7
8
9
10 11 12
0 to 100
400 to 500
0 to 50
0
0
0
0
0
0
0
0 to 200
400 to 600
0 to 100
0
0
0
1
0 to 400
400 to 800
0 to 200
0
0
1
0
0 to 800
400 to 1200
0 to 400
0
0
1
1
0 to 125
400 to 525
-50 to 50
0
1
0
0
0
0
0
K
0 to 250
400 to 650
-50 to 100
0
1
0
1
0
0
1
J
0 to 500
400 to 900
-50 to 200
0
1
1
0
0
1
0
R
0 to 1000
400 to 1400 -50 to 400
0
1
1
1
0
1
1
S
0 to 150
400 to 550
-100 to 50
1
0
0
0
1
0
0
N
0 to 300
400 to 700 -100 to 100 1
0
0
1
1
0
1
E
0 to 600
400 to 1000 -100 to 200 1
0
1
0
1
1
0
B
0 to 1200*
400 to 1600 -100 to 400 1
0
1
1
1
1
1
T
0 to 175
400 to 575
-200 to 50
1
1
0
0
0 to 350
400 to 750 -200 to 100 1
1
0
1
0 to 700
400 to 1100 -200 to 200 1
1
1
0
0 to 1400** 400 to 1800 -200 to 400 1
1
1
1
0
0
0
Linearisation ON 0
Linearisation off 1
* n/a for types N and E
CJC ON 0
** n/a for types K, J, N and E
CJC off 1
Temperature Range in °C
Switch S1 for Thermocouple Input
T/C
Type
Then select the required setting from the table below for switch S2
Thermocouple
1
2
3
4
5
6
7
8
9
10 11 12
All Ranges
0
1
0
0
1
1
1
0
0
0
0
0
Switch S2
!
! WARNING !
DO NOT OPEN UNIT OR ADJUST SWITCHES WITH
POWER SUPPLY, INPUT OR OUTPUT CONNECTED
Please note that PC Software is available to provide information on
switch settings for your input and output requirements.
Page
10
IIG-010801