Calibrating the isocon – B&B Electronics ISOCON-6 - Manual User Manual

Page 13

background image

ISOCON-6 USERS GUIDE

5. CALIBRATING THE ISOCON

When the unit is shipped the ISOCON will be calibrated for the input and output
types and ranges noted on the side label. If this label is blank then the unit will be
calibrated for 4-20mA input and 4-20mA source output.

If the unit is re-ranged by the user it is necessary to re-calibrate the unit to obtain the
maximum accuracy. The calibration is achieved by using both switches on the front
panel to select the zero or span input and then using the switches as raise/lower
buttons to adjust the output to the value required.

The mode the unit is in is indicated by the colour of the LED:

Green

-

Normal Operation

Red

- Span

Adjust

Yellow - Zero

Adjust


Setting of the zero and span points is non-interactive, so each point need only be set
once. A typical calibration sequence would be as follows:


LED Colour Mode

Action

Green Normal

Apply full scale input.
Press and release both buttons together to enter
span mode

RED Span

Adjust

Press raise / lower buttons to adjust output value
Press and release both buttons together to return
to normal mode

Green Normal

Apply zero scale input
Press and release both buttons together to enter
zero mode

YELLOW Zero

Adjust

Press raise / lower buttons to adjust output value
Press and release both buttons together to return
to normal mode

Green Normal

Use

product


The unit is now calibrated and ready for use.

Note: The unit will retain the new settings on power down.



IIG-010801 Page

13