beautypg.com

Rtd input, 6 rtd, Input – B&B Electronics ISOCON-6 - Manual User Manual

Page 11: 6 rtd input

background image

ISOCON-6 USERS GUIDE

4.1.6 RTD Input

Select the range from the table below and set Switch S1 to the required values.

Range in °C

1

2

3

4

5

6

7

8

9

10 11 12

0 to 100

0

0

0

0

0

0

1

0

0

0 to 200

0

0

0

1

0 to 400

0

0

1

0

0 to 800

0

0

1

1

-50 to 50

0

1

0

0

-50 to 150

0

1

0

1

-50 to 250

0

1

1

0

-50 to 350

0

1

1

1

-100 to 50

1

0

0

0

-100 to 100

1

0

0

1

-100 to 200

1

0

1

0

-100 to 400

1

0

1

1

-200 to 200

1

1

0

0

-200 to 400

1

1

0

1

-200 to 600

1

1

1

0

-200 to 800

1

1

1

1

0

0

1

0

0

RTD linearisation ON

0

PT100

0

RTD linearisation off

1

PT1000

1

RTD 2 or 4 wire 0

RTD 3 wire 1

Switch S1

And then select the required setting from the table below for switch S2

RTD

1

2

3

4

5

6

7

8

9

10 11 12

2 Wire RTD

0

1

0

0

1

0

0

1

0

0

0

1

3 Wire RTD

0

1

0

0

0

0

0

0

1

0

0

1

4 Wire RTD

0

1

0

0

0

0

0

1

0

1

0

0

Switch S2

!

! WARNING !

DO NOT OPEN UNIT OR ADJUST SWITCHES WITH

POWER SUPPLY, INPUT OR OUTPUT CONNECTED

Please note that PC Software is available to provide information on

switch settings for your input and output requirements.


IIG-010801 Page