12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
MAX16070/MAX16071
______________________________________________________________________________________ 27
Table
16. Reset Output Configuration
REGISTER
ADDRESS
FLASH
ADDRESS
BIT RANGE
DESCRIPTION
3Bh
23Bh
[1:0]
Reset output depends on:
00 = Undervoltage threshold violations
01 = Early warning threshold violations
10 = Overvoltage threshold violations
11 = Undervoltage or overvoltage threshold violations
[2]
0 = Active-low
1 = Active-high
[3]
0 = Push-pull
1 = Open drain
[7:4]
Reset timeout period
0000 = 25μs
0001 = 1.5ms
0010 = 2.5ms
0011 = 4ms
0100 = 6ms
0101 = 10ms
0110 = 15ms
0111 = 25ms
1000 = 40ms
1001 = 60ms
1010 = 100ms
1011 = 150ms
1100 = 250ms
1101 = 400ms
1110 = 600ms
1111 = 1s
3Ch
23Ch
[0]
Reset soft trigger
0 = Normal RESET behavior
1 = Force RESET to assert
[1]
1 = RESET depends on MON1
[2]
1 = RESET depends on MON2
[3]
1 = RESET depends on MON3
[4]
1 = RESET depends on MON4
[5]
1 = RESET depends on MON5
[6]
1 = RESET depends on MON6
[7]
1 = RESET depends on MON7
3Dh
23Dh
[0]
1 = RESET depends on MON8
[1]
1 = RESET depends on MON9
[2]
1 = RESET depends on MON10
[3]
1 = RESET depends on MON11
[4]
1 = RESET depends on MON12
[7:5]
Reserved