Electronics LP-24 User Manual
Page 5
![background image](/manuals/278811/5/background.png)
5
Fig. 2 An air cylinder was used to
open and close the original mechanical
valve as shown. This air cylinder was
controlled by a manually operated 2-
way air valve. The air cylinder moves
the mechanical valve from its closed to
open position. The amount of opening
was pre-set by the operator by adjust-
ing a nut on the linkage of the air cylin-
der to limit the stroke.
Fig. 3 This figure shows an ammeter
reading of approximately 8 amps, the
no-load or no shot flow condition. A
conventional panel ammeter (0-30
Amps) was used to indicate motor
amps and relative shot flow rate. It is
not uncommon for these meters to be
inaccurate because metallic dust col-
lects inside the meter movement mech-
anism. This prevents the meter from
displaying the proper amperage.
Fig. 2
Fig. 3
- Pot-24 (2 pages)
- WM 3000-24 (2 pages)
- WM 3000-24 (10 pages)
- 500-P (10 pages)
- 500-P (2 pages)
- LP2000VAR (2 pages)
- FC (2 pages)
- FC (21 pages)
- LP2000_VAR (2 pages)
- LP2000_VAR (13 pages)
- VLP1000_VAR (2 pages)
- LP-24 (2 pages)
- 576-24 (2 pages)
- AC (2 pages)
- AC (25 pages)
- 578-24 (2 pages)
- 590 (8 pages)
- 590 (2 pages)
- 590-24 (2 pages)
- 590-24 (26 pages)
- 577 (2 pages)
- FC-24 (2 pages)
- FC-24 (12 pages)
- 190-AC (2 pages)
- 100 (2 pages)
- VLP-24 (2 pages)
- 0-120 Vac Variac (1 page)
- AC-24 (16 pages)
- AC-24 (2 pages)
- MC (12 pages)
- MC (2 pages)
- 179-AC (2 pages)
- VLP1000 (2 pages)
- 580-24 (2 pages)
- 178-DC (2 pages)
- 577-24 (2 pages)
- 500-24 (6 pages)
- 500-24 (2 pages)
- 180-AC (2 pages)
- LP2000 (2 pages)
- VLP1000VAR (2 pages)