Electronics LP-24 User Manual

Page 2

background image

2

WHEEL
MOTOR

WIRE CONNECTIONS FOR VLP-24 OR LP-24 TO AN AC-24 AMPERAGE CONTROLLER

L1

L2

L3

Customer CT
100:5 etc.

0-5 amps

Current Shunt
.05 ohm 5 watt.
P/N 999200
Included with
controller.

NOTE : The valve must be located as close to the wheel

as possible for best servo control stability.
( 5 feet or closer)

0

100

(0-5A)

PANEL METER

(IF USED)

www.magnavalve.com

Remote setpoint can come
from customer potentiometer
or 0-10 Vdc signal. Also see
model Pot-24 remote pot.

7

5

2

CW

*

0 Vdc
common

.05 Ohm shunt

.05 Ohm shunt

VLP-24 Orange

VLP-24 Blue

+24Vdc to VLP-24 RED

0Vdc to VLP-24 BLACK

Note: Connect power supply directly to the MagnaValve first and then run power back to the control using minimum 16 AWG
wire size to prevent (high current ) voltage drops. Power supply should be regulated and rated at 50VA per valve.

Alternate: Long length of current loop may cause
inaccuracy. To keep the 0-5 Amp current loop short
you may place the .05 ohm shunt at the transformer
terminals and run 18AWG shielded cable from shunt
to control.

NOTE: The Controller's Full Scale display (typical
100.0) must match the customer's current
transformer rating (typical 100:5 ratio). Adjust the
control display range to match the actual
transformer ratio. See instruction manual.

1

2

4

5

6

3

1. WHITE
2. RED
3. GREEN
4. ORANGE
5. BLACK
6. BLUE

VLP-24/LP-24
4) Orange 0-10 Vdc input
6) Blue 24 Vdc Enable
2) Red 24 Vdc Supply
5) Black 0 Vdc Common

AC-24 Controller
8) Servo Out
9) Valve Enable
19) 24 Vdc Supply
20) 0 Vdc Common

Use 12 AWG wire for current loop. Use
10 AWG or larger for runs over 15 ft.

AC-24 Rear Terminal