6 Setup - radar sensors from software 4.0.0
PLICSCOM •
36433-EN-130228
5. Set the requested numerical value with [+] and [->]
6. Push
[OK]
Note:
During simulation, the simulated value is outputted as Profibus PA
signal.
How to interrupt the simulation:
→
Push [ESC]
Information:
The simulation is automatically terminated 10 minutes after the last
press of a key.
In this menu item, you define the unit of the Secondary Values 2
(SV2):
In this menu item, the sensor address is adjusted on Profibus PA.
An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-
dress can be used for function test of the instrument and for con-
nection to a Profibus PA network. Then address must be changed to
integrate additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
Note:
The software addressing is only possible if address 126 or higher is
adjusted on the instrument with the address selection switches.
Additional adjustments/
Unit SV2
Additional adjustments/
Sensor address