beautypg.com

VEGA PLICSCOM User Manual

Page 17

background image

17

5 Setup - Sensors up to software 3.99

PLICSCOM •

36433-EN-130228

Information:

The trend recording is not activated when being shipped. It must be

started by the user via the menu item "Start trend curve".

A comparison of the echo curve and the false echo curve allows a

more detailled evaluation of measurement reliability. The selected

curve is updated continuously. With the [OK] key, a submenu with

zoom functions is opened.
The following functions are available with "Echo and false echo

curve":

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

In the menu item "Trend curve" the following are available:

"X-Zoom": Resolution

– 1 minute

– 1 hour

– 1 day

"Stop/Start": Interrupt a recording or start a new recording

"Unzoom": Reset the resolution to minutes

As default setting, the recording pattern has 1 minute. With the adjust-

ment software PACTware, this pattern can be also set to 1 hour or 1

day.

Echo curve

In this menu item you simulate a user-defined level or pressure value

via the current output. This allows you to test the signal path, e.g.

through connected indicating instruments or the input card of the

control system.
The following simulation variables are available:

Percent

Current

Pressure (with pressure transmitters)

Distance (with radar and guided microwave)

With Profibus PA sensors, the selection of the simulated value is

made via the "Channel" in the menu "Basic adjustments".
How to start the simulation:
1. Push

[OK]

2. Select the requested simulation variable with [->] and confirm

with [OK].

3. Set the requested numerical value with [+] and [->].
4. Push

[OK]

Diagnosis/Curve presen-

tation

Service/Simulation