6 Setup - radar sensors from software 4.0.0

PLICSCOM •

36433-EN-130228

In the menu item "Display" you can define which measured value

should be presented on the display.
The sensor delivers the following measured values:

PV (Primary Value): Linearised percentage value

SV1 (Secondary Value 1): Percentage value after the adjustment

SV2 (Secondary Value 2): Distance value before the adjustment

AI FB1 (OUT)

AI FB2 (OUT)

AI FB3 (OUT)

Height

In this menu item you simulate measured values via the signal output.

Hence, the signal path can be tested via the segment coupler up to

the input card of the control system.

How to start the simulation:
1. Push

[OK]

2. Select the requested simulation variable with [->] and confirm

with [OK].

3. With

[OK] you start the simulation, first of all the actual measured

value is displayed in %

4. Start the editing mode with [OK]

Display/Displayed value

Diagnosis/Simulation