10 Maintenance and fault rectification
VEGAMET 391 • With SIL qualification
38704-EN-130228
Error code Cause
Rectification
E015
Sensor in boot phase
Sensor current
< 3.6 mA or line
break
– Check sensor, e.g. on failure
– Remove line break
– Check connection of the sensor
E017
Adjustment span too
small
– Carry out a fresh adjustment and
increase the distance between min.
and max. adjustment
E021
Scaling span too
small
– Carry out a fresh scaling, increase
the distance between min. and max.
scaling.
E034
EEPROM CRC error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E035
ROM CRC error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E037
RAM error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E040
Hardware error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E062
Pulse priority too
small
– Increase under "Output" the entry
"Pulse output all" so that max. one
pulse per second is outputted.
E080
Microcontroller error
– Switch the instrument off and on
– Carry out a reset
– Send instrument for repair
E110
Relay switching
points too close to-
gether
– Increase the difference between the
two relay switching points
E111
Relay switching
points interchanged
– Change relay switching points for
"On/Off"
E113
Hardware error, cur-
rent output
– Switch the instrument off and on
– Shortcircuit terminals of the unused
current output
– Send instrument for repair
E115
Several relays are as-
signef to the pump
control which are not
set to the same fail-
ure mode
– All relays which are assigned to the
pump control must be set to the
same failure mode
E116
Several relays that
are not configured
with the same mode
are assigned to the
pump control
– All relays which are assigned to the
pump control must be set to the
same mode