beautypg.com

VEGA VEGAMET 391 With SIL qualification User Manual

Page 39

background image

39

9 Application examples

VEGAMET 391 • With SIL qualification

38704-EN-130228

tank". After that, a linearization must not be carried out on the signal

conditioning instrument.

To display the volume in litres, you have to enter in the signal con-

ditioning instrument under "Measurement loop - Scaling" as unit

"Volume" in litres. Then the allocation is carried out, in this example

100 % ≙ 10000 litres and 0 % ≙ 0 litres.

The mode of relay 3 must be set to mode "Dry run protection". The

switching points are set as follows:

Switch-on point (switching point Hi) 40 % ≙ 10.4 mA

Switch-off point (switching point Lo) 5 % ≙ 4.8 mA

In this example, the vessel can be emptied until the relay switches off

when 5 % are reached and the emptying pump thus switches off. If

the level rises again to over 40 %, the relay is switched on and empty-

ing begins again.
Information:

The switch-on and switch-off points of the relays must not be set to

the same switching point because this would cause a continuous

switching on and switching off when this threshold is reached. Hence,

this setting is not accepted and a corresponding error message is

outputted. To avoid this effect also with a fluctuating product surface,

setting a difference (hysteresis) of 5 % between the switching points

is a good idea.

9.3 Pump control 1/2 (running time controlled)

Pump control 1/2 is used to control several pumps with the same

function dependent on the previous running time. Always the pump

with the shortest running time is switched on and the pump with

the longest running time switched off. With increased requirement,

all pumps can also run at the same time dependent on the entered

switching points. With this measure, a steady utilization of the pumps

is achieved and the reliability increased.
All relays with activated pump control are not assigned to a certain

switching point but are switched on or off depending on the accu-

mulated operating time. The signal conditioning instrument selects

the relay with the shortest operating time when the switch-on point

is reached and the relay with the longest operating time when the

switch-off point is reached.
Probable failures of the pumps can be processed in addition via the

digital inputs.
With this pump control, there are two different versions:

Pump control 1: The upper switching point determines the switch-

off point for the relay, whereas the lower switching point deter-

mines the switch-on point

Pump control 2: The upper switching point determines the switch-

on point for the relay, whereas the lower switching point deter-

mines the switch-off point

Scaling

Relay

Functional principle