beautypg.com

VEGA VEGAMET 391 With SIL qualification User Manual

Page 24

background image

24

7 Setup with the integrated display and adjustment unit

VEGAMET 391 • With SIL qualification

38704-EN-130228

Overfill protection: Relay is switched off when the max. level is

exceeded (safe currentless condition), relay is switched on again

when the level falls below the min. level (switch-on point < switch-

off point)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless condition), relay is switched

on again when the max. level is exceeded (switch-on point >

switch-off point)

Pump control: With several pumps having the same function, the

pumps will be alternately switch on and off according to the adjust-

able criteria

Additional modes such as "Switching window", "Flow" and "Tenden-

cy" can be only adjusted via PACTware and DTM.
Relay 2 can be alternatively configured as fail safe relay. The follow-

ing example shows the adjustment of an overfill protection. Further

information to pump control are available in chapter "Application

examples".

Select the requested mode and save with [OK]. By pushing [->], you

reach the next menu item.
1. Now enter the reference value to which the relay switching points

relate. By pushing [->], you reach the next menu item.

2. Now enter the switching points for switching the relay on and off.

In the following window the reaction of the relay in case of failure can

be determined. Here you can define whether, in case of failure, the

switching condition of the relay remains unchanged or the relay is

switched off.