beautypg.com

2 dry run protection according to sil2 – VEGA VEGAMET 391 With SIL qualification User Manual

Page 37

background image

37

9 Application examples

VEGAMET 391 • With SIL qualification

38704-EN-130228

the guided microwave. Filling is carried out by a pump controlled via

a PLC. Relay 3 of VEGAMET is connected to prevent overfilling. The

max. filling should be at 90 % level, which corresponds to 9538 litres

in a standard vessel (according to sounding chart). The filling quantity

should be displayed in litres.

Carry out the adjustment as described in the respective operating

instructions of the sensor. After that, further adjustment must not be

carried out on the signal conditioning instrument.

To have the percentage volume displayed correctly, a lineariza-

tion must be carried out. As described in the respective operating

instructions of the sensor, select the linearization curve "Cylindrical

tank". After that, a linearization must not be carried out on the signal

conditioning instrument.

To display the volume in litres, you have to enter in the signal con-

ditioning instrument under "Measurement loop - Scaling" as unit

"Volume" in litres. Then the allocation is carried out, in this example

100 % ≙ 10000 litres and 0 % ≙ 0 litres.

The mode of relay 3 must be set to mode "Overfill protection". The

switching points are set as follows:

Switch-off point (switching point Hi) 90 % ≙ 18.4 mA

Switch-on point (switching point Lo) 60 % ≙ 13.6 mA

In this example, the vessel can be filled until the relay switches off

when 90% are reached and thus the filling pump switches off. If the

level falls below 60%, the relay is switched on again and thus enabled

for the filling process.
Information:

The switch-on and switch-off points of the relays must not be set to

the same switching point because this would cause a continuous

switching on and switching off when this threshold is reached. Hence,

this setting is not accepted and a corresponding error message is

outputted. To avoid this effect also with a fluctuating product surface,

setting a difference (hysteresis) of 5 % between the switching points

is a good idea.

9.2 Dry run protection according to SIL2

The described setup of sensor and VEGAMET is specified as dry run

protection according to SIL2. Filling and emptying are realized via a

separate control (e.g. PLC).
The level is detected via a sensor and transfered by means of the

4 … 20 mA signal to the signal conditioning instrument. To prevent

dry run, the SIL relay integrated in the signal conditioning instrument

switches off the emptying pump when the level falls below the adjust-

able switching threshold.
Due to the geometrical form of the spherical tank, the vessel volume

does not increase linearly with the level. This can be compensated for

by selecting the linearization curve integrated in the sensor. It speci-

Adjustment

Linearisation

Scaling

Relay

Functional principle