Output results

7.1

Display

7.1.1 Allocation of a multiplication factor

If an indication in flow m

3

/h is requested, first an allocation

of a multiplication factor to the measured level 0 % and
100 % must be carried out in mode

0 - 13

and

0 - 14

.

This allocation of a multiplication factor is only valid for the
indication and does not influence the output results for the
relay and current outputs.

7.1.2 Measuring unit

In mode

0 - 15

first of all the level proportional indication is

converted to a linearized, flow percentage indication,
derived from the allocation of a multiplication factor.

Furthermore different measuring units can be inserted as
label into the respective window.

7.1.3 Decimal point

Furthermore the position of the decimal point can be
determined in mode

0 - 16

.

7 Output results

Programming example

Allocation of a multiplier for 0 %
• Enquire mode

0 - 13

in the MODEFIELD

• Program the figure

0000

in the PARAMETER FIELD

• Then store with STO

On display 1 the actual distance of

0.525

m is indicated at

the moment.

Allocation of a multiplier for 100 %
• Enquire mode

0 - 14

in the MODEFIELD

• Program the figure

7500

in the PARAMETER FIELD

• Then store with STO

On display 1 still the actual distance of

0.525

m is

indicated.

Measuring unit and label
• Enquire mode

0 - 15

in the MODEFIELD

• Program the figure

3

in the PARAMETER FIELD

• Then store with STO

On the display 15 % (linearized value) of the previously
programmed allocation of a multiplier are indicated (

112.5

).

Position of the decimal point
• Enquire mode

0 - 16

in the MODEFIELD

• Shift with key –> the position of the decimal point to the

right until the requested position is reached

• Then store with STO

The desired form is indicated on the display (

11.25

). Insert

the label m

3

/h into the window.

0.350

0.525

0.700

100

50

0

100

15

0

= 75.00

11.25

= 00.00

0 - 14

0 - 13

11.25

Mode

0-15

=

1

0-15

=

2

0-15

=

3

distance level

flow

in m

in %

in %

Flow acc. to
allocation of a
multiplier in m

3

/h