VEGASON 71 - D

18

5 Adjustment

5

Adjustment

5.1

Empty / full adjustment in metres without flow change

With this adjustment procedure two distances in m are defined which correspond to the levels of 0 % and 100 %.

5.2

Demonstration and programming example

Demonstration

0.000

0.350

0.700 0

100

m %

0.7 m distance ^ 0 %

0.35 m distance ^ 100 %

Programming example

0.350 m distance ^ 100 %
• Enquire mode

0 - 12

in the MODEFIELD

• Program

0.350

m in the PARAMETER FIELD

• Then store with key STO

0.700 m distance ^ 0 %
• Enquire mode

0 - 11

in the MODEFIELD

• Program

0.700

m in the PARAMETER FIELD

• Then store with key STO

(The sequence of the empty and full adjustment is individual)