Diagnosis
9.5 Error codes
Error code
Meaning
E004
This operation is not supported by the instrument (different software versions).
You have tried to activate a function with a newer software version of VEGA
Visual Operating in an instrument with an older software version. However, the
instrument cannot support this operation.
Have the software of your instrument updated.
E014
Possible short-circuit
Probable reasons:
- short-circuit
- sensor is defective
Check the connection cable and, if necessary, the sensor.
Also possible:
- an incorrect measuring range has been set on the capacitive electrode.
Set a smaller range.
E015
Possible short-circuit
Probable reasons:
- no sensor connected
- line break
- sensor is defective
Check the connection cable and, if necessary, the sensor.
E016
Empty/full adjustment reversed. The values for the empty adjustment are
above the values for the full adjustment. Carry out the adjustment again.
E017
Adjustment span too small. The adjustment values are too close together or are
identical. Carry out the adjustment again.
Also possible:
- an incorrect measuring range has been set on the capacitive electrode.
Adjust a higher range.
E021
Span of the scaling values too small or values reversed. The scaling values are
too close together or are identical. Please check the scaling.
E022
Scaling span too big.
E027
Actual measured value is less than -10 %.
E028
Actual measured value is more than 110 %.
E029
Measured value is simulated. The measured value is generated by simulation
and does not reflect the actual status.
E031
Same DISBUS address. At least one other instrument with the same DISBUS
address is connected to the DISBUS. Please check the DISBUS address.