Mounting
2 Mounting
VEGAMET 515 signal conditioning instru-
ments can be either mounted with a module
in a carrier BGT 596 or BGT 596 Ex.M or in a
single housing type 505.
Mounting in carrier
Mount the respective module (standard or Ex
version) in your carrier. Wire the connection
of the multipoint connector according to the
wiring plan.
Module
Multipoint connector DIN 41 612, series F, 33-
pole (d, b, z) with coded pins and mounting
material for mounting in carrier BGT 596 or
BGT 596 Ex.M.
Module Ex
Multipoint connector DIN 41 612, series F, 33-
pole (d, b, z) with coded pins, Ex separating
chamber and mounting material for mounting
in carrier BGT 596 Ex.M.
The multipoint connector is available in the
following versions:
- Wire-Wrap standard connection
1.0 x 1.0 mm
- Plug connection 2.8 x 0.8 mm
- Termi-Point standard connection
1.6 x 0.8 mm
- Soldering connection
- Screw terminals 2 x 0.5 mm
2
For further mounting information, see the
operating instructions of the carrier.
Mounting in single housing
Either screw the housing socket directly to
the mounting plate or plug onto a carrier rail
(35 x 15 acc. to EN 50 022 or 32 acc. to
EN 50 035). Connect the terminals according
to the wiring plans on the following pages.
For further mounting information, see the
operating instructions of the housing.
Transparent cover
To protect the instrument against unauthor-
ised adjustment, the front plate of VEGAMET
can be provided with a lockable transparent
cover (supplied with the instrument).
Coding
To prevent an interchanging of the different
signal conditioning instruments, the multipoint
connector of carrier or the housing can be
equipped with coded pins.
Note:
The coding is absolutely necessary for Ex
instruments!
The multiple plug of the signal conditioning
instrument is equipped with respective holes
(mechanical coding). Instrument coding
ensures that the different signal conditioning
instruments are not interchanged. The appro-
priate coded pins are supplied with each
module or housing. Equip the multipoint con-
nector with these coded pins acc. to the