6.6 Monitoring
To activate monitoring, the following
prerequirements must be met:
Meas.
value 50
%
High 5 %
Low –5 %
>55 %
Relay
deenergises
<45%
Configuration
• Choose in the menu item "
Input from
“ (un-
der the menu item "
Monitoring
“) input 4.
• Connect a key switch (opener) to input 4.
Confi-
gura-
tion
Config
inputs
Config
meas.
loop
TAG 1
Level
Appli-
cation
Level
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Moni-
toring
Input
from
Input
no.4
• Choose in the menu range "
Parameter
adjustment relay outputs
“ in the menu item
"
Mode
“ the mode "
Monitoring
“ for the se-
lected relay.
The selected relay activates. By pushing the
key switch (opener opens), the actual meas-
ured value is first of all frozen and, derived
from this, the relay deactivates if this value is
underrun (Low) or exceeded (High). After a
reset and a repeated push of the key switch,
the actual measured value is again frozen.
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Adjust-
ment
Signal
condit-
ioning
Out-
puts
Curr.
out-
puts
Volt
outputs
Relay
outputs
Relay
output1
prop.
to
Per-
cent
Unit
0,0%
Mode
(moni-
toring)
Low
%
5,0
High
%
5,0
Monit.
to
Low &
High
If the monitoring function has to be deacti-
vated, monitoring must first be cancelled in
the menu item "
Mode
“. Then, the allocation of
the correction input (input 4) must be can-
celled under the menu item "
Monitoring
“.