beautypg.com

VEGA VEGAMET 515 User Manual

Page 44

background image

44

VEGAMET 515

Relay mode "overfill protection"

The relay deenergises at switching point
"High“ (safe condition).

Relay mode "dry run protection"

The relay deenergises at switching point
"Low“ (safe condition).

Relay mode "switching window on"

The relay is energised within the switching
window.

Relay mode "switching window off"

The relay is deenergised within the switching
window.

Relay mode "monitoring"

The enquired relay energises. By pushing
the key switch (opener) the actual measured
value is first of all frozen and, derived from
this, the relay deactivates if this value is
underrun (LOW) or exceeded (High). After a
reset and a repeated push of the key switch,
the actual measured value is frozen again.

Parameter adjustment

d

t

b z

High

Low

Relay output

Parameter

d

t

b z

High

Low

Relay output

Parameter

d

t

b z

High

Low

Relay output

Parameter

d

t

b z

High

Low

Relay output

Parameter

Meas. value
50 %

High 5 %

Low –5 %

>55 %

Relay
deenergised

<45%