beautypg.com

VEGA VEGASON 54P…56P Profibus PA User Manual

Page 43

background image

VEGASON 54P … 56P

43

Setup

Ampl.:

XX dB

S-N:

XX dB

8. Signal and noise level

In the menu

you get important information on the signal
quality of the product echo. The higher the
"S-N" value, the more reliable the measure-
ment (menu schematic MINICOM).

Ampl.:

means amplitude of the level echo in
dB (useful level)

S-N:

means Signal-Noise, i.e. the useful
level minus the level of the back-
ground noise

The bigger the "S-N" value (difference be-
tween the amplitudes of the useful signal level
and the noise level), the better the measure-
ment:
> 50 dB

Measurement excellent

40 … 50 dB

Measurement very good

20 … 40 dB

Measurement good

10 … 20 dB

Measurement satisfactory

5 … 10 dB

Measurement sufficient

< 5 dB

Measurement poor

Example:

Ampl. = 68 dB
S-N = 53 dB

68 dB – 53 dB = 15 dB noise level

A signal distance of 53 dB means a very high
degree of measurement reliability.

9. Outputs

Under the menu "Outputs" you determine, for
example, if the current output should be
inverted, or which unit of measurement
should be shown on the sensor display.