beautypg.com

3 measurement of liquids, Flat vessel top – VEGA VEGASON 54P…56P Profibus PA User Manual

Page 17

background image

VEGASON 54P … 56P

17

< 100 mm

It is also possible to mount version C sensors
in a 1" thread.

2.3 Measurement of liquids

Flat vessel top

On flat vessels, mounting is usually done on
a very short DIN socket piece. The lower
side of the flange is the reference plane. The
transducer should protrude out of the flange
pipe.

VEGASON 55 in flange version on short DIN socket
piece

Reference plane

Mounting and installation

Min. distance
Type 54: 1 m
Type 55: 0.8 m

< 400 mm

VEGASON 56 in flange version on short DIN socket
piece

Reference plane

Min. distance
1.8 m

A mounting location directly on the vessel top
is ideal. A round opening in the vessel top is
sufficient to fasten the sensor with the flange
or version B and C with the swivelling holder.

Flange version and swivelling holder on flat vessel
top

Reference
plane

Reference
plane

< 60 mm

Mounting of the transducer in a 1" thread

Reference plane

Min. meas. distance

1.8 m

Min. meas. dis-

tance 1.4 m

Swivelling
holder