Buildup, Inflowing material, Vessel installations – VEGA VEGASON 54P…56P Profibus PA User Manual

Page 22: Struts

background image

22

VEGASON 54P … 56P

Buildup

If the sensor is mounted too close to the
vessel wall, residues or buildup of the meas-
ured product on the vessel wall can cause
false echoes. Position the sensor at a suffi-
cient distance from the vessel wall. Please
also note chapter "2.2 General installation
instructions".

Inflowing material

Do not mount the instrument in or above the
filling stream. Ensure that you detect the
product surface and not the inflowing mate-
rial.

Mounting and installation

Vessel installations

Vessel installations such as, for example, a
ladder, often cause false echoes. Make sure
when planning your measurement loop that
the ultrasonic signals have free access to the
measured product.

Vessel installations

Correct

Incorrect

Ladder

Ladder

Struts

Struts, like other vessel installations, can
cause strong false echoes that are superim-
posed over the useful echo signal. Small
shields effectively hinder a direct false echo
reflection. The false echoes are scattered
and diffused in the area and are then filtered
out as "echo noise" by the measuring elec-
tronics.

Struts

Correct

Incorrect

Shields

Inflowing material

Correct

Incorrect

Correct

Incorrect