beautypg.com

Adjustment with adjustment module minicom, Adjustment with the simatic pdm adjustment program, Adjustment with pactware – VEGA VEGASON 54P…56P Profibus PA User Manual

Page 10: Product description, Pactware, Can be found in the pactware

background image

10

VEGASON 54P … 56P

Product description

Detachable adjustment module MINICOM

-

+

ESC

OK

Tank 1

m (d)
12.345

Adjustment with adjustment module
MINICOM

With the small (3.2 cm x 6.7 cm) 6-key ad-
justment module with display, you carry out
the adjustment in clear text dialogue. The
adjustment module can be plugged into the
ultrasonic sensor or into the optional, external
indicating instrument.

The adjustment module can be easily re-
moved to prevent unauthorised sensor ad-
justment.

Adjustment with detachable adjustment module. The
adjustment module can be plugged into the ultrasonic
sensor or into the external indicating instrument
VEGADIS 50.

max. 2.5 m

Adjustment with the SIMATIC PDM
adjustment program

To adjust all essential functions of the VEGA
sensor with the adjustment station SIMATIC
PDM from Siemens, a so-called EDD is re-
quired. Without this EDD, only the basic func-
tions such as min./max. wet adjustment or
integration time can be adjusted with the
PDM adjustment program. Further important
adjustment functions, such as input of the
measuring environment or false echo stor-
age, are not available without EDD. After
integration of the EDD files in the Simatic PDM
adjustment software, all important adjustment
functions are accessible. If it is not at hand,
the obligatory GSD (instrument master file)
as well as the EDD (Electronic Device De-
scription) necessary for PDM can be
downloaded from the VEGA homepage
(http://www.vega.com).

Adjustment with PACTware

TM

PACTware

TM

is a manufacturer-independent

automation/configuration tool through which
access to instruments of different manufac-
turers (Krohne, Pepperl + Fuchs, VEGA,
WIKA-, Bürkert…) is possible. The VEGA
adjustment software VVO works as a
subprogram/menu. PACTware

TM

activates the

required menu options for the sensor/instru-
ment being accessed.

PACTware

TM

looks different than VVO and is

designed with a tree structure. Operating
instructions for PACTware

TM

can be found in

the PACTware

TM

documentation. They are not

described in this operating instructions
manual.

2

4

-

+

ESC

OK

Tank 1
m (d)
12.345

-

+

ESC

OK

Tank 1
m (d)
12.345

PA-Bus