Current transducers, voltage output, Medium current ranges, Po wer metering ct s

background image

P

O

WER Metering CT

S

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Medium Current Ranges

DESCRIPTION

The E682x and H681x-V Series of current transducers provide a safe voltage output
for use with data loggers, chart recorders, and power monitoring equipment. E682x
devices are solid-core with 0-0.333VAC output, while H681x CTs are split-core and
have 0-0.333VAC and 1VAC output options.

APPLICATIONS

Data logging

Recording

Power monitoring

Energy management

Alternative energy monitoring

Cost allocation

Current Transducers,

Voltage Output

SPECIFICATIONS (Solid-Core)

Inputs:

Frequency Range

50/60 Hz

Leads

6’ (1.8 m)

Accuracy:

Accuracy

±0.5% of reading from 5% to 120% of rated current

Outputs:

Output at Rated Current 0.333VAC

Mechanical:

Insulation

600VAC

Environmental:

Operating Temperature Range

-40° to 85°C (40° to 185°F)

Storage Temperature Range

-50° to 105°C (-58° to 221°F)

Humidity Range

0-95% noncondensing

Installation Category

Cat III, pollution degree 2

Agency Approvals

UL61010-1, EN61010-1

SPECIFICATIONS (Split-Core)

Inputs:

Frequency Range

50/60 Hz

Leads

6 ft (1.8 m)

Accuracy:

Accuracy

±1% of reading from 10% to 100% of rated current

Outputs:

Output at Rated Current

0.333 or 1VAC

Mechanical:

Insulation

600VAC

Environmental:

Operating Temperature Range

2400A models only: -15° to 50°C (5° to 122°F); All other models: -15° to 60°C (5° to 140°F)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Humidity Range

0-95% noncondensing

Agency Approvals

UL61010, EN61010

H681x-V

E682x & H681x-V SERIES

FEATURES

High accuracy: ±0.5% from 5% to 120% of rated current for E682x or ±1%

from 10% to 100% of rated current for H681x

0.333V and 1VAC output versions available

UL recognized

E682x

HQ0001818.D 01131