Veris Industries TP SERIES Datasheet User Manual
Flush mount temperature sensors, Durable device for temperature monitoring, Tp series
TE
MPERA
TURE
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
TP
Durable Device for Temperature
Monitoring
Flush Mount
Temperature Sensors
TP SERIES
FEATURES
●
Wiring is potted...resistant to moisture
●
Stainless steel construction...durable
●
Mounts to standard duplex wall mount box...easy installation
●
Easy to clean
●
Available with linitemp, RTD, or thermistors...application flexibility
DESCRIPTION
TP flush mounted temperature sensors are designed to monitor the temperature
of the air in areas where sensor durability and security are needed. They are ideal
for spaces where moisture and vapor are concerns. The back of the TP is insulated
to reduce interior wall temperature influence. The TP is for indoor use only, and it is
warranted for a period of five years.
SPECIFICATIONS
Wiring
22 AWG; 2-wire: RTD Thermistor, 4-20mA; 3-wire: Voltage output models
Housing
Brushed 430 stainless steel
Linitemp:
Input Power
5 to 30VDC
Output
1µA/°C or 10mV/°C
Operating Temperature
-25° to 105°C (-13° to 221°F)
Resistive:
RTD/Thermistor
See table, facing page
Accuracy:
Calibration Error
1.5°C (2.7°F) typical; 2.5°C (4.5°F) max. at 25°C (77°F)*
Error over Temperature
1.8°C (3.24°F) typical; 3.0°C (5.4°F) max. over 0° to 70°C (32° to 158°F) range;
2.0°C (3.6°F) typical, 3.5°C (6.3°F) max. over -25° to 105°C (-13° to 221°F) range
*Room temperature error documented on each unit.
HQ0003998.A 01131