Z202851-0D

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

03121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

V100

INSTALLATION GUIDE

N.C.

Common

10-30VAC/DC

120VAC

HI

wht/black

LOW

wht/blue

COMM

wht/yellow

Common

N.O.

CONTACT OUTPUT

CONTROL SYSTEM INPUT

White

YELLOW

White

White

ORANGE

blac

k

blac

k

blue

blue

yello

w

yello

w

blac

k

WIRING EXAMPLE

Nipple mount directly to a panel

Nipple mount to any 2x or 4x electrical box

To Load

To Controls

COIL

CONT

ACTS

To Load

To Controls

Wire
Nut

CO

IL

CONTACTS

WIRING COLOR CODES

CONTACT AND COIL SPECIFICATIONS

Pull in Voltage

AC

DC

10-30V..................................... 8

9

120V........................................ 78
Drop Out Voltage

AC

DC

10-30V..................................... 2 3

120V........................................ 18
Voltage

Coil Current

AC DC

10V.......................................... 25mA 14mA

12V.......................................... 25mA 14mA

24V.......................................... 31mA 16mA

30V.......................................... 39mA 18mA

120V........................................ 22mA

-

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.

240VAC, 1/3HP N.O. & 1/6HP N.C.

277VAC, 1/4HP N.O. & 1/8HP N.C.

Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes