ENVIRONMENTAL SENSORS
INSTALLATION GUIDE
CO Alarm Verification Test Kit
AA32/AA39
AA32/AA39
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PRODUCT IDENTIFICATION
Part Number
Description
AA32
Kit with 100 ppm CO, 17 Liter bottle
AA39
Kit with 100 ppm CO, 103 Liter bottle (requires special regulator valve)
OPERATION
The CO verification test kit is used to test that the G series CO sensor is functioning
correctly. The kit includes a bottle of 100 ppm CO gas and tubing to connect this to
the G series sensor. During testing, the actual concentration of CO flowing into the
sensor is diluted by mixing with air.
INSTALLATION
Preparation
Power the sensor for 96 hours prior to verification. Check that the green LED is
steadily lit before proceeding. If not, contact technical support.
Verification
1. Connect regulator valve to CO bottle.
2. Fill humidifier reservoir half full with water.
3. Screw brass barb onto inlet hole at the bottom right of the sensor. To protect the
sensing element, do not screw brass barb flush to the sensor housing.
4. Attach 2 ft. tubing between CO bottle and humidifier.
5. Attach 6 ft. tubing between humidifier and brass barb.
6. Slowly open regulator valve.
7. Allow CO gas to flow for 7 minutes. If the sensor is functioning, the red LED will
turn on after approximately 3 minutes and remain steadily lit (not flashing).
8. Close regulator valve. Disconnect tubing from brass barb and disassemble the
verification test kit.
Carbon Mono
xide Sensor
GX SERIES
CARBON
MONOXIDE
GAS
Brass Barb
3/8" driver
Regulator
Valve
Humidifier