Veris Industries HW PROTOCOL SERIES Datasheet User Manual
Modbus and bacnet protocol communication, Hw protocol series, Hu midit y

HU
MIDIT
Y
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Deluxe Wall Humidity &
Temperature Sensor,
Protocol Communication
FEATURES
●
Embedded BACnet and Modbus communication protocols...compatible with
many existing control systems
●
Configurable to multiple baud rates
●
Humidity and temperature sensors in one device at one address...provides
more information and maximizes system capacity
●
Pushbutton override capability from the building control system...local control
in individual rooms to maximize comfort
●
Innovative self-calibration algorithm...maximizes performance
●
Field calibratable
●
Thin-film capacitive sensor element recovers from 100% saturation
●
Fully interchangeable element to 1% or 2% accuracy...no calibration
●
Calibration-free interchangeable NIST traceable HS element
●
HS element is microprocessor profiled with on-board nonvolatile memory
●
Multi-point digital calibration to NIST standards
●
NIST certification available
●
Replace element in the field...minimizes field calibration downtime
DESCRIPTION
HW Protocol Series Deluxe humidity transmitters provide an ideal solution for
measuring relative humidity in all conditions. All devices are equipped with a
thin-film capacitive sensor that is easily replaceable in the field. These sensors are
calibrated to NIST standards, with certificates available.
The HWLP features embedded BACnet and Modbus communication protocols with
humidity and temperature sensing capability. The setpoint slider and pushbutton
override offer additional local control.
The wall-mounted HWLP model features a low-profile housing with an LCD display
for local indication. All models come with a standard five-year warranty.
†
APPLICATIONS
●
Office buildings, schools, or other systems utilizing BACnet or Modbus protocol
SPECIFICATIONS
Input Power
12 to 30VDC, 24VAC; 100mA max.
Housing Material
High impact ABS plastic , UL 94 VO
Communication:
Protocol
BACnet or Modbus (selectable)
Connection
2-wire RS-485
Data Rate
9600, 19200, 38400, 57600 (Modbus), bps (selectable); 9600, 19200, 38400, 76800 (BACnet), bps (selectable)
Parity
None/Odd/Even (selectable-Modbus); None (BACnet)
Address Range 1-127
Humidity:
HS Element
Replaceable digitally profiled thin-film capacitive; (32-bit mathematics); U.S. Patent 5,844,138 †
Accuracy*
±2% from 10 to 80% RH; NIST traceable multi-point calibration
Reset Rate**
24 hours
Stability
±1 @20°C (68°F) annually for two years
Hysteresis
1.5% typical
Operating Humidity Range
0 to 100% RH noncondensing
Operating Temperature Range
10° to 35°C (50° to 95°F)
Temperature Coefficient
±0.1% RH/°C above or below 25°C (typical)
Operating Environment:
Operating Temperature Range
10° to 35°C (50° to 95°F)
Temperature Transmitter Option:
Sensor Type
Solid-state, integrated circuit
Accuracy
±0.5°C (±1°F) typical
Resolution
0.1°C (0.2°F)
Range
10° to 35°C (50° to 95°F)
Setpoint Slider Resolution Option
1% full scale
Override Button Option
Remotely readable and resettable
† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
* Specified accuracy with 24VDC supplied power with rising humidity.
** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
Note: RTD/Thermistors in wall packages are not compensated for internal heating of product.
EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2007 specification requirements)
Modbus and BACnet
Protocol Communication
HWLP
HW PROTOCOL SERIES
HQ0001723.B 01131