background image

Z202856-0C

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

04121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

V400

INSTALLATION GUIDE

WIRING EXAMPLE

Nipple mount directly to a panel

Nipple mount to a 2x or 4x electrical box

WIRING COLOR CODES

CONTACT AND COIL SPECIFICATIONS

*Contact ratings are for single pole operation. When
operating both poles simultaneousley, the total load
cannot exceed the ratings above.

Pull in Voltage

AC DC

20-30V..................................... 18

20

208-277V................................. 186
Drop Out Voltage

AC

DC

20-30V..................................... 4

5

208-277V................................. 44
Voltage

Coil Current

AC DC

24V.......................................... 43mA 25mA

30V.......................................... 54mA 31mA

208V........................................ 27mA

-

277V........................................ 36mA

-

TYPICAL

COIL PERFORMANCE

CONTACT RATINGS*

Resistive.............. 10A@277VAC, 30VDC
Motor.................... 120VAC, 1/8HP

N.C.

Common

20-30VAC/DC

LOW

wht/blue

COMM

wht/yellow

Common

N.O.

CONTACT OUTPUT

CONTROL SYSTEM INPUT

White

YELLOW

White

ORANGE

blue

blue

yello

w

yello

w

N.C.

Common

N.O.

208-277VAC

HI

wht/brown

White

brow

n

brow

n

* Isolate any unused wires, e.g. wire nut.

To Load A

To Controls

CONTROL

PANEL

COIL

To Load B

To Power

COM

N.O.

N.C.

To Load B

To Control

Wire
Nuts

CO

IL

CONTACTS

To Load A

To Power

N.C.

N.O.

COM