Installation guide, Typical coil performance contact ratings, Wiring example – Veris Industries V400 SERIES Install User Manual
Page 2: Wiring color codes contact and coil specifications, V400

Z202856-0C
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
04121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
V400
INSTALLATION GUIDE
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
*Contact ratings are for single pole operation. When
operating both poles simultaneousley, the total load
cannot exceed the ratings above.
Pull in Voltage
AC DC
20-30V..................................... 18
20
208-277V................................. 186
Drop Out Voltage
AC
DC
20-30V..................................... 4
5
208-277V................................. 44
Voltage
Coil Current
AC DC
24V.......................................... 43mA 25mA
30V.......................................... 54mA 31mA
208V........................................ 27mA
-
277V........................................ 36mA
-
TYPICAL
COIL PERFORMANCE
CONTACT RATINGS*
Resistive.............. 10A@277VAC, 30VDC
Motor.................... 120VAC, 1/8HP
N.C.
Common
20-30VAC/DC
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUT
CONTROL SYSTEM INPUT
White
YELLOW
White
ORANGE
blue
blue
yello
w
yello
w
N.C.
Common
N.O.
208-277VAC
HI
wht/brown
White
brow
n
brow
n
* Isolate any unused wires, e.g. wire nut.
To Load A
To Controls
CONTROL
PANEL
COIL
To Load B
To Power
COM
N.O.
N.C.
To Load B
To Control
Wire
Nuts
CO
IL
CONTACTS
To Load A
To Power
N.C.
N.O.
COM