Typical coil performance contact ratings, Installation guide, Hoa positions wiring example – Veris Industries V103 Install User Manual
Page 2: Wiring color codes contact and coil specifications

Z203393-0D
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
05121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
V103
INSTALLATION GUIDE
HOA POSITIONS
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
To Load
To Controls
COIL
CONT
ACTS
To Load
To Controls
Wire
Nut
CO
IL
CONTACTS
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
Pull in Voltage
AC DC
10-30V..................................... 8
9
120V........................................ 78
Drop Out Voltage
AC
DC
10-30V..................................... 2 3
120V........................................ 18
Voltage
Coil Current
AC DC
10V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
120V........................................ 22mA
-
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@277VAC
Motor.................... 1/3HP@120VAC
Gold Flash............. Yes
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
Digital HOA Position Monitor
10-30VAC/DC
120VAC
LOW
wht/blue
COMM
wht/yellow
HI
wht/black
CONTACT OUTPUT
CONTROL SYSTEM INPUT
Common