Veris Industries CD SERIES Install User Manual
Cd series, Notice, Duct mounted environmental co

ENVIRONMENTAL SENSORS
Z204900-0K
PAGE 1
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
06114
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
Duct Mounted Environmental CO
2
Sensors
Installer’s Specifications
Input Voltage
20 to 30VDC, 24AC
Analog Output
CDE models: 4-20mA (clipped & capped)/0-10VDC (selectable)
CDL
models: 4-20mA (clipped & capped)/0-5VDC/0-10VDC (selectable)
Sensor Current Draw
100mA Maximum
Operating Temperature Range
0° to 50°C (32° to 122°F)
Operating Humidity Range
0-95% (noncondensing)
Housing Material
High impact ABS plastic
CO2 Transmitter:
Sensor Type
Non-dispersive infrared (NDIR), diffusion sampling
Output Range
0-2000 ppm or 0-5000 ppm, user selectable on CDL models,
0-2000 ppm on CDE models
Accuracy
±30 ppm ±2% of measured value*
Repeatability
±20 ppm ±1% of measured value
Response Time
<60 seconds for 90% step change
RH Transmitter**:
HS Sensor Digitally profiled thin-film capacitive (32-bit mathematics); U.S. Patent 5,844,138
Accuracy
±2% from 10 to 80% RH @ 25°C; Multi-point calibration NIST
Hysteresis
1.5% typical
Linearity
Included in Accuracy spec.
Stability
±1% @ 20°C (68°F) annually, for two years
Output Range
0 to 100% RH
Temperature Coefficient
±0.1% RH/°C above or below 25°C (typical)
Temperature (Transmitter)**:
Sensor Type
Solid-state, integrated circuit
Accuracy
±0.5°C (±1°F) typical
Resolution
0.1°C (0.2°F)
Output Range
10° to 35°C (50° to 95°F)
Relay Contacts**:
1 Form C
1A@30VDC, resistive; 30W max.
Specified accuracy with 24VDC supplied power with rising humidity. RTD/Thermistors in wall
packages are not compensated for internal heating of product.
EMC Conformance: EN 61000-6-3:2001 (Amended by A11:2004) Class B, EN 61000-6-1:2001
EMC Test Methods: CISPR 22:2006, IEC 61000-4-2:2001, IEC 61000-4-3:2006, IEC 61000-4-4:2004,
IEC 61000-4-6:2006, IEC 61000-4-8:2001, IEC 61000-4-11:2004
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor
with proper Surge protection (EN 61000-6-1:2001 specification requirements).
* Measured at NTP
** Not available on CDE
Note: Rough handling and transportation may cause a temporary reduction of CO
2
sensor
accuracy. With time, the ABC function will tune the readings back to the correct accuracy range.
The default tuning speed is limited to 30 ppm per week.
CD SerieS
CD SerieS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
CDE
CDL
QUICK INSTALL
1. Using the mounting diagram on page 2, or using the housing as a template, mark
and drill the four mounting holes on the duct. The centerline through the housing
must be parallel to the air flow through the duct.
2. Rotate the duct probe so that its widest surface is perpendicular to the air flow in
the duct.
3. Insert the probe and secure the sensor to the duct with the sheet metal screws
provided, making sure that the provided gasket material is compressed between
the sensor housing and the air duct.
4. Wiring. See wiring diagrams on next page.
PRODUCT IDENTIFICATION
RH Option
H = RH2%
X = NO RH
CDL
DELUXE MODEL:
S
Temp
T = Temp
X = No Temp
(Stop Here)
Sensor Type
A = Transmitter
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, RTD, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
Optional Cal Cert.
Blank = None
1 = 1 pt Temp Cert
2 = 2 pt Temp Cert
CDE
(no options)
ECONOMY MODEL:
DIMENSIONS
6.7"
(170 mm)
3.1"
(78 mm)
7.8"
(97 mm)
2.4"
(61 mm)
10.2"
(258 mm)