Veris Industries V400 SERIES Datasheet User Manual
Enclosed victory relays: 10a dpdt, Dpdt relays provide versatility, Typical coil performance contact ratings

REL
AY
S
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Enclosed Victory Relays:
10A DPDT
FEATURES
●
Sleek field enclosure reduces the need for panel space
●
The nipple mount feature allows the Victory Series to be mounted to any
electrical enclosure
●
Flexible tinned stranded wire...fits easily in tight spaces and provides secure
connections to wire nuts
●
UL508 Listed...designed and listed for field installation...makes electrical
inspection a snap
DESCRIPTION
The Victory 300 and 400 Series 10A DPDT pilot duty enclosed relays combine
industrial strength and ease of use. The nipple mount enclosure makes installation
easy. With no need for a dedicated field enclosure, they are the ideal retrofit devices.
One coil input controls the state of two pilot rated contacts for the simultaneous
control of two devices or both poles of a single-phase circuit, e.g. motor loads.
Field-selectable high and low voltage coil inputs provide on-site versatility.
APPLICATIONS
●
Command contactors
●
Control motors
●
Isolation
●
Device interlocking
●
Relay logic
●
Sense voltages for alarm conditions
SPECIFICATIONS
Operating Temperature Range
-34° to 60°C (-29° to 140°F)
Operating Humidity Range
10-90% RH non-condensing
Expected Relay Life
Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles
Relay Status
LED ON=energized
Wire Specifications:
Lead Length
14” (356 mm) min.
Gauge
UL1015; Coil: 18 AWG; Contacts: 16 AWG
Insulation Class
600VAC RMS
Agency Approvals
UL 508
DPDT Relays Provide Versatility
Year
Warranty
5
V400
V300
*Contact ratings are for single pole operation. When
operating both poles simultaneousley, the total load
cannot exceed the ratings above.
Pull in Voltage
AC DC
20-30V..................................... 18
20
120V........................................ 104
208-277V................................. 186
Drop Out Voltage
AC
DC
20-30V..................................... 4
5
120V........................................ 26
208-277V................................. 44
Voltage
Coil Current
AC DC
24V.......................................... 43mA 25mA
30V.......................................... 54mA 31mA
120V........................................ 29mA
-
208V........................................ 27mA
-
277V........................................ 36mA
-
TYPICAL
COIL PERFORMANCE
CONTACT RATINGS*
Resistive.............. 10A@277VAC, 30VDC
Motor.................... 120VAC, 1/8HP
VICTORY 300 & 400
HQ0001839.B 01131