beautypg.com

Caution, Installation guide, Operation – Veris Industries H722HC Install User Manual

Page 2: Wiring, Calibration/scaling, H722hc, For load currents less than sensor minimum rating, Amperage range selector switch

background image

6%2)3

INSTALLATION GUIDE

H722HC

Z202942-0A

PAGE 2

©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

09083

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

300A:

5A

300A

5A

50A

Controller:

CT max ÷ H722HC max

300 ÷ 50 = 6x

300 A

200
100
50

opEration

The H722HC is a current transducer that senses current (amperage) in any of three
field-selectable ranges: 0-50, 0-100, or 0-200 amperes. These ranges represent
the maximum current that can be applied to the monitored conductor. The H722HC
transforms the monitored current into a 0-5VDC output suitable for connection to
building controllers or other appropriate data acquisition equipment. The H722HC
requires no external power to generate its output.

notEs

troublEshooting

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.

• Controller must be
programmed to account
for the extra turns. e.g., if
four turns pass through
the sensor (as shown) the
normal controller reading
must be divided by 4.

< 5A (H722HC min.)

4A

4x

50A

Controller: 10A/volt
Amps ÷ Turns
(16A ÷ 4) = 4A

1.6V

(16A)

4A

200
100
50

DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H681x-5A CT

> 200A (H722HC max.)

For load currents greater than sensor maximum rating:

Use a 5 Amp (H681x series) Current Transformer (CT) as shown.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of

turns through the sensing window using the following

formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps

e.g. : 30A ÷ 4 Turns = 7.5 Amps max. in monitored conductor

Failure to follow these instructions can result in overheating

and permanent equipment damage.

Problem

Solution

No Reading at Controller

• Confirm measured current is within the selected

range on the product.

• Check polarity of sensor output connections.

Wiring

Amperage Range
Selector Switch

200
100
50

200
100
50

calibration/scaling

Set the amperage range selector switch to a level appropriate for your load. The
H722HC is available with three choices, 0-50, 0-100, or 0-200 Amps.

SENSED AMPS

Selected Range*

0 VDC

0A

5 VDC

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

DDC

CONTROLLER

AI

COMM

0-5VDC Input

CAUTION: Consult
instructions prior
to installation

!

Use min. 75º C insulated conductor

ig20

AMPERAGE

RANGE

40
20
10

OUTPUT
0-10VDC

+ –

+

Self-Powered Output

Scale the output as shown below.

10x