Installation guide, Typical coil performance contact ratings, Wiring example – Veris Industries V120 Install User Manual
Page 2: Wiring color codes contact and coil specifications, V120, Nipple mount directly to a panel, Nipple mount to 4x electrical box, Power source

Z203094-0D
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
04122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
V120
INSTALLATION GUIDE
WIRING EXAMPLE
Nipple mount directly to a panel
To Load
To Controls
COIL
CONT
ACTS
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
Nipple mount to 4x electrical box
Voltage
Coil Current
AC DC
24V.......................................... 75mA 32mA
120V........................................ 42mA
-
TYPICAL
COIL
PERFORMANCE
CONTACT RATINGS
Resistive.............. 20A@277VAC, 28VDC
Motor.................... 120VAC, 1HP
277VAC, 2HP
Pilot Duty............. A300
Ballast.................. 277VAC, 20A N.O.
277VAC, 10A N.C.
Tungsten............... 120VAC, 10A N.O.
120VAC, 2A N.C.
To Controls
POWER
SOURCE
Fractional
HP Motor
N.C.
Common
24VAC/DC
120VAC
HI
wht/black
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUT
CONTROL SYSTEM INPUT
White
YELLOW
White
White
ORANGE
blac
k
blac
k
blue
blue
yello
w
yello
w
blac
k