H8920-3

INSTALLATION GUIDE

NETWORK VARIABLE DETAILS

Name

Type

Range

Description

nv1

nvoEgyWH

0-1e38kWH

Total Accumulated Energy

nv2

nvoPower

0-1e38kW

Power

nv3

nvoVAR

0-1e38kW

Reactive Power

nv4

nvoVA

0-1e38kW

Apparent Power

nv5

nvoPF

0-1

Power Factor

nv6

nvoLLVolts

0-1e38V

Voltage, Line to Line

nv7

nvoLNVolts

0-1e38V

Voltage, Line to Neutral

nv8

nvoAmps

0-1e38A

Amps

nv9

nvoAPower

0-1e38kW

Power, Phase A

nv10

nvoBPower

0-1e38kW

Power, Phase B

nv11

nvoCPower

0-1e38kW

Power, Phase C

nv12

nvoAPF

0-1

Power Factor, Phase A

nv13

nvoBPF

0-1

Power Factor, Phase B

nv14

nvoCPF

0-1

Power Factor, Phase C

nv15

nvoABVolts

0-1e38V

Voltage, Phase A to Phase B

nv16

nvoBCVolts

0-1e38V

Voltage, Phase B to Phase C

nv17

nvoACVolts

0-1e38V

Voltage, Phase A to Phase C

nv18

nvoANVolts

0-1e38V

Voltage, Phase A to Neutral

nv19

nvoBNVolts

0-1e38V

Voltage, Phase B to Neutral

nv20

nvoCNVolts

0-1e38V

Voltage, Phase C to Neutral

nv21

nvoAAmps

0-1e38A

Amperage, Phase A

nv22

nvoBAamps

0-1e38A

Amperage, Phase B

nv23

nvoCAmps

0-1e38A

Amperage, Phase C

nv24

nvoDmdSubInt

0-1e38kW

Present Real Subinterval Demand

nv25

nvoCurrDmd

0-1e38kW

Current Real Demand

nv26

nvoPeakDmd

0-1e38kW

Peak Real Demand

nv27

nvoRDmdSubInt

0-1e38kW

Present Reactive Subinterval Demand

nv28

nvoRCurrDmd

0-1e38kW

Current Reactive Demand

nv29

nvoRPeakDmd

0-1e38kW

Peak Reactive Demand

nv30

nviSubIntLen

0-65535

* Length of Subinterval multiplied by 5 sec.

nv31

nviNumSubInts

0-6

* Number of Subintervals per Demand

nv32

nviCommand

0-65535

* Command Register

nv33

nviMeterIndex

1-63

Selects Modbus address

nv34

nvoMeterIndex

1-63

Reports selected Modbus address

nc49

nciMaxSendT

0.0-6553.4 sec

Maximum time between nvoPower updates. Default is 0 sec (disabled).

nc52

nciMinSendT

0.0-6553.4 sec

Minimum time between nvoPower updates. Default is 15 sec.

nc88

nciMinDelta

0.0-100.0%

Percent change in nvoPower that will force an nvoPower update. Default is 5%. Set to 0.0% to disable.

nc49

nciMaxSendTg

0.0-6553.4 sec

Maximum time between updates to all network variables. Default is 0 sec (disabled).

* See H8163-CB documentation for further details. Do not bind to these meter configuration variable, because demand calculation restarts each time the meter writes these variables, and bound
variables are re-written at regular intervals.