Caution, Installation guide, Operation – Veris Industries H600 Install User Manual
Page 2: Troubleshooting

TM
INSTALLATION GUIDE
H600
Z201983-0K
PAGE 2
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
03132
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
OPERATION
The H600 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in amperage in the monitored conductor
that crosses the switch (setpoint) threshold plus the hysteresis value causes the
resistance of the FET status output to change state, similar to the action of a
mechanical switch. In this model, the setpoint is fixed at 150 mA AC max. (200 mA for
50 Hz operation). The status output is suitable for connection to building controllers
or other appropriate data acquisition equipment operating at up to 30 volts. The
H600 requires no external power supply to generate its output.
TROUBLESHOOTING
Problem
Solution
No Reading at Controller
• Check for control voltage at sensor (<30V)
• Check for amperage in monitored conductor (> 0.15A
@ 60Hz)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's
instructions. Terminate the CT secondary before applying
current.
H68xx‑5A CT
240A
300A:
5A
4A
> 200A (Sensor max.)
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
< 0.15 A (Sensor Min.)
4x
0.5A
0.1A
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be
combined with wrapping (see below) when added range is desired for a low current
load on a high current source.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns through the center window. This increases the current
measured by the transducer.
Program the controller to account for the
extra turns. e.g., if four turns pass through the
sensor (as shown) divide the normal controller
reading by 4.