beautypg.com

Typical coil performance contact ratings, Installation guide, Hoa positions wiring example – Veris Industries V201D Install User Manual

Page 2: Wiring color codes contact and coil specifications, V201d, Relay 1 relay 2, Hand off auto

background image

Z203419-0B

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

04121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

V201D

INSTALLATION GUIDE

HOA POSITIONS

WIRING EXAMPLE

Nipple mount directly to a panel

Nipple mount to a 2x or 4x electrical box

To Load

To Controls

COIL

CONT

ACTS

To Load

To Controls

Wire
Nut

CO

IL

CONTACTS

WIRING COLOR CODES

CONTACT AND COIL SPECIFICATIONS

Pull in Voltage

AC DC

10-30V..................................... 8

9

207-277V................................. 154
Drop Out Voltage

AC

DC

10-30V..................................... 2 3

208-277V................................. 36
Voltage

Coil Current

AC DC

10V.......................................... 25mA 14mA

24V.......................................... 31mA 16mA

30V.......................................... 39mA 18mA

208V........................................ 19mA -

277V........................................ 25mA -

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive.............. 10A@250VAC
Motor.................... 1/3HP@120VAC
Gold Flash............. Yes

HAND
OFF
AUTO

Up position: contacts are closed.

Middle position: contacts are open.

Down position: control system actuates the contacts.

Relay 1

Relay 2

N.C.

Common

10-30VAC/DC

208-277VAC

HI

wht/orange

LOW

grey/wht

COMM

wht/violet

Common

N.O.

CONTACT OUTPUT

CONTROL SYSTEM INPUT

Grey

VIOLET

White

White

BROWN

ora

nge

ora

nge

whit

e

whit

e

viole

t

viole

t

GREY