Veris Industries H81xx SERIES Datasheet User Manual
Energy meters, H81xx series, Po wer/ener g y monit oring
p
o
wer/ener
g
y monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Simple System Integration with a
Variety of Protocol Options Available
Energy Meters
FEATURES
●
Revenue Grade measurements
●
High resolution backlit LCD display provides clear readings at a distance...
reduces the risk of misinterpretation of the data. Back-lighting can be disabled
if desired
●
H8163 provides a pulse output from 1/10 to 1 pulse per kWh for easy connection
to existing control or data acquisition systems
●
Provides a phase-loss alarm...protects equipment (H8163)
●
With the optional communications board (H81xx-CB), the H81xx can easily be
added to a Modbus, BACnet or N2 control system network to report multiple
variables including kW, kWh, kVAR, PF, Amps and Volts, providing crucial power
information at a reduced installation cost
DESCRIPTION
The H81xx Series Energy Meters are easy to install and provide exceptional system
accuracy, making them ideal for all submetering applications.
Each meter is factory-matched with one to three split-core CTs. The meter/CT pairs
are system-calibrated to provide excellent total system accuracies of 1% from 2%
to 100% of the amperage rating of the CTs (e.g., 2-100 amps with 100 amp CTs).
Matching serial numbers assure that the meter and CT were calibrated together
(matching does not apply if using 100A CTs).
The H81xx is easy to install. The split-core CTs eliminate the need to remove
electrical conductors, reducing installation time. The meter is also capable of
detecting and correcting phase reversal, eliminating the need for concern about
CT load orientation. The convenient color coding of the CTs and voltage leads make
correct connection simple.
APPLICATIONS
●
Commercial tenant submetering
●
Performance contracting
●
Allocating costs
●
Real-time power monitoring via local display or through control/data
acquisition systems
SPECIFICATIONS
Inputs:
Voltage Input
H8150
90-132VAC line-to-neutral
H8163
90-300VAC line-to-neutral
Accuracy:
System Accuracy
±1% of reading from 2% to 100% of the rated current of the CTs, accomplished by matching the CTs with electronics and calibrating them as a system
Sample Rate
1280 Hz
Outputs:
All Models
LCD Display
1.2” x 3.8” (31 mm x 97 mm) viewing area, 160 segments, backlit with LCD
H8163 Only
Pulse Output
Normally open, Opto-FET, 100mA@24VAC/DC
Pulse Rate
0.10*, 0.25**, 0.50, or 1.00kWh per pulse
Pulse Width
200 msec closed
Phase Loss Alarm
N.O. (opens on alarm), Opto-FET, 100 mA @ 24 VAC/DC; fixed threshold 25% below
Mechanical:
Protection Class
NEMA 1
Environmental:
Operating Temperature Range
0° to 50°C (32° to 122°F)
Storage Temperature Range
-40° to 70°C (-40° to 158°F)
Humidity Range
0-95% noncondensing
Agency Approvals UL61010
Approved for California CSI Solar applications (check the CSI website for model numbers).
*not supported at >1600A
**not supported at >2400A
Note: Meter and CTs serial numbers must match, except for 100A CTs. Neutral voltage connection is required.
H81xx
Year
Warranty
5
H81xx SERIES
HQ0001813.B 01131